Services

Today, business runs & grows by the service factor.

We highly welcome your queries and it will receive our prompt attention all the times.

FAQs

Yes, all gas valves are provided is on set position so there is no worry for setting the burner on site.

Yes all our burners are ‘Plug & Play’. You just have to give power supply and fuel supply. You also can see how to give fuel supply and power supply in our burner operating manual.

There are four potential causes of this issue:

  1. Check the photocell, remove (disconnect) from sequence Controller. Re-fit it in controller and fire up burner. If it fires after 12 secs and then locks out after 5 secs, the photocell is faulty. Also check the photocell cleanliness and unobstructed.
  2. Check the pressure of oil. Oil Pressure should be 10-15kg if not it may cause this problem. For proper oil pressure, put the oil day tank at a height of at least 10 feet from the burner.
  3. Check the air. Excess air may cause the lockout of burner also. Set the air from air damper.
  4. As a last resort, change the sequence controller.

If your burner problem not solved from above questions or you have another queries. Please contact to our customer care no. +91 92288 55679